SM333
Circuit Breakers
CIRCUIT BREAKER
SM333
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.375 inches
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Frequency In Hertz
400.0
-
Bushing Length
0.375 inches maximum
-
Body Length
1.500 inches maximum
-
Body Width
1.875 inches maximum
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 150 pct and 9.000 maximum at 150 pct and 1.000 minimum at 200 pct and 3.500 maximum at 200 pct and 0.200 minimum at 300 pct and 1.000 maximum at 300 pct and 0.010 minimum at 400 pct and 0.100 maximum at 400 pct
-
Thread Series Designator
unef
-
Terminal Type And Quantity
6 wire hook