510B302R
Circuit Breakers
CIRCUIT BREAKER
510B302R
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
05869-711520 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Bushing Length
0.300 inches minimum and 0.320 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Switch Current Rating And Type In Amps
10.0 ac and 3.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Body Style
single pole type
-
Switch Terminal Type
pin
-
Frequency In Hertz
60.0 single location
-
Thread Series Designator
unef
-
Mounting Surface To Terminal End Distance
1.700 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Center To Center Distance Between Terminals Parallel To Length
0.844 inches minimum and 0.906 inches maximum
-
Body Width
0.640 inches maximum
-
Auxiliary Switch Function And Quantity
1 alarm
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.500 minimum at 200 pct single location and 8.000 maximum at 200 pct single location
-
Switch Location And Position Designation
internal at pole one
-
Inclosure Protection Type For Which Designed
shockproof and hermetically sealed and vibrationproof and corrosion resistant and moisture resistant
-
Fragility Factor
moderately rugged
-
Trip Release Method
magnetic single location
-
Terminal Type And Quantity
2 wire hook
-
Special Handling Feature
magnetic
-
Unpackaged Unit Weight
1.800 ounces
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac single location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Body Length
1.760 inches maximum
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Circuit Protection Type