50-166-1

Circuit Breakers

CIRCUIT BREAKER

50-166-1

5925-00-925-3833

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Continuous Load Current Rating Per Pole

    7.5 amperes ac single location

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Operating Voltage Type And Rating Per Pole In Volts

    125.0 ac single location

  • Terminal Type And Quantity

    2 threaded stud

  • Switch Current Rating And Type In Amps

    5.0 ac and 1.0 dc

  • Actuator Function

    trip-reset

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.320 minimum at 200 pct single location and 0.960 maximum at 200 pct single location

  • Switch Voltage Rating And Type In Volts

    125.0 ac and 50.0 dc

  • Center To Center Distance Between Terminals Parallel To Length

    3.053 inches minimum and 3.073 inches maximum

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Circuit Protection Type

    overcurrent single location

  • Switch Contact Arrangement

    single pole, double throw

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

  • Body Length

    3.709 inches minimum and 3.729 inches maximum

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof

  • Trip Release Characteristic

    time delay single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.740 inches minimum and 2.760 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 ac single location

  • Body Style

    single pole type

  • Trip Release Method

    magnetic-hydraulic single location

  • Frequency In Hertz

    60.0 single location

  • Body Width

    0.980 inches minimum and 1.000 inches maximum

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Boss Height

    0.146 inches minimum and 0.166 inches maximum

  • Switch Terminal Type

    tab, solder lug

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Mounting Surface To Terminal End Distance

    3.239 inches nominal

  • Storage Type

    general purpose warehouse

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...