7274-25-2
Circuit Breakers
CIRCUIT BREAKER
7274-25-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Function
reset
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Terminal Type And Quantity
2 screw
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Bushing Length
0.359 inches nominal
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Manual Actuator Type And Quantity
1 push-pull
-
Test Data Document
96906-ms26574 standard (includes industry or association standards, individual manufactureer standards, etc.).
-
Pole Quantity
1
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.437 inches
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac single location and 28.0 dc single location
-
Inclosure Protection Type For Which Designed
explosion proof
-
Trip Release Characteristic
time delay single location
-
Body Width
0.580 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac single location and 2.0 amperes dc single location
-
Frequency In Hertz
400.0 single location
-
Body Style
single pole type
-
Body Length
0.780 inches maximum
-
Trip Release Method
magnetic-hydraulic single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
800.0 ac single location and 800.0 dc single location
-
Center To Center Distance Between Terminals Parallel To Length
0.593 inches nominal
-
Thread Series Designator
uns
-
Case Material
plastic
-
Mounting Surface To Terminal End Distance
1.420 inches maximum