SM3-20DC2
Circuit Breakers
CIRCUIT BREAKER
SM3-20DC2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
81349-mil-c-39019 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 single location
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches maximum
-
Body Style
single pole type
-
Body Width
0.625 inches maximum
-
Thread Series Designator
unef
-
Mounting Surface To Terminal End Distance
1.700 inches maximum
-
~1
data on certain environmental and performanc
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.055 minimum at 200 pct single location and 0.950 maximum at 200 pct single location and 0.240 maximum at 400 pct single location
-
Fragility Factor
moderately rugged
-
Trip Release Method
magnetic single location
-
Terminal Type And Quantity
2 wire hook
-
Bushing Length
0.332 inches minimum and 0.380 inches maximum
-
Reset Method
manual
-
Ultimate Trip Time Per Pole In Seconds
0.200 minimum single location and 7.000 maximum single location
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Thread Pitch Diameters
+0.3503/+0.3537 inches
-
Inclosure Protection Type For Which Designed
fungus resistant and hermetically sealed
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Specification/Standard Data
81349-mil-c-39019/1 government specification
-
Circuit Protection Type
overcurrent single location
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes dc single location
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Body Length
1.562 inches maximum