HE3-C2-C2-C3-2-240-1
Circuit Breakers
CIRCUIT BREAKER
HE3-C2-C2-C3-2-240-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
1.495 inches nominal
-
Body Width
1.872 inches nominal
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Mounting Surface To Terminal End Distance
1.678 inches nominal
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Storage Type
general purpose warehouse
-
Special Handling Feature
magnetic
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Auxiliary Switch Function And Quantity
2 control
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.375 inches
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Switch Terminal Type
tab,solder lug
-
Switch Current Rating And Type In Amps
1.0 ac and 0.5 dc
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Test Data Document
97942-128c099 drawing
-
Thread Series Designator
unef
-
Terminal Type And Quantity
6 wire hook
-
Thread Pitch Diameters
p0.3503/p0.3537 inches
-
Bushing Length
0.375 inches nominal
-
Switch Contact Arrangement
single pole,double throw
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Arc Quenching Method
magnetic blowout
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0
-
Ultimate Trip Time Per Pole In Seconds
6.500 minimum and 30.000 maximum
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct and 4.000 maximum at 200 pct
-
Frequency In Hertz
400.0