8648139-4
Circuit Breakers
CIRCUIT BREAKER
8648139-4
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Internal Trip Release Configuration
series trip second location
-
Switch Location And Position Designation
external at pole three
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.230 minimum at 200 pct and 0.700 maximum at 200 pct all locations
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Switch Terminal Type
turret
-
Switch Current Rating And Type In Amps
2.5 ac and 1.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Unpackaged Unit Weight
14.000 ounces
-
Thread Series Designator
unc
-
Terminal Type And Quantity
8 threaded stud
-
Internal Trip Release Configuration
relay trip third location
-
Body Length
2.530 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.060 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Mounting Surface To Terminal End Distance
3.000 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Thread Quantity Per Inch
32
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Body Style
8c multipole-multiple actuator type
-
Body Width
2.280 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Boss Height
0.150 inches nominal
-
Storage Type
general purpose warehouse
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Auxiliary Switch Function And Quantity
1 alarm
-
Internal Trip Release Configuration
series trip first location
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
400.0