00C2

Circuit Breakers

CIRCUIT BREAKER

00C2

5925-00-938-1017

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.120 minimum at 200 pct all locations and 0.550 maximum at 200 pct

  • Nominal Thread Size

    0.375 inches

  • Actuator Position Designation

    at pole two

  • Actuator Function

    trip-reset

  • Main Contact Tripping Mechanism Type

    trip free

  • Reset Method

    manual

  • Ultimate Trip Time Per Pole In Seconds

    0.850 minimum all locations and 5.000 maximum

  • Trip Release Characteristic

    time delay all locations

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Continuous Load Current Rating Per Pole

    20.0 amperes ac all locations and 20.0 amperes dc

  • Arc Quenching Method

    magnetic blowout

  • Pole Quantity

    3

  • Fragility Factor

    moderately rugged

  • Center To Center Distance Between Terminals Parallel To Length

    0.865 inches minimum and 0.885 inches maximum

  • Body Width

    1.844 inches minimum and 1.906 inches maximum

  • Body Style

    1b multipole-single actuator type

  • Terminal Type And Quantity

    4 wire hook

  • Thread Series Designator

    unef

  • Frequency In Hertz

    400.0 all locations

  • Inclosure Protection Type For Which Designed

    fungus resistant and hermetically sealed

  • Internal Trip Release Configuration

    series trip all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    magnetic all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac all locations and 750.0 dc

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations and 50.0 dc

  • Thread Quantity Per Inch

    32

  • Storage Type

    general purpose warehouse

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Mounting Surface To Terminal End Distance

    1.690 inches minimum and 1.710 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.615 inches minimum and 0.635 inches maximum

  • Case Material

    metal

  • Body Length

    1.552 inches minimum and 1.572 inches maximum

  • Bushing Length

    0.365 inches minimum and 0.385 inches maximum

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...