SW324
Circuit Breakers
CIRCUIT BREAKER
SW324
The Technical Material Corporation
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
19b multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
4 threaded stud
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Body Length
5.250 inches nominal
-
Body Width
3.000 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
4.359 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.062 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.000 inches nominal
-
Boss Height
0.218 inches nominal
-
Mounting Surface To Terminal End Distance
3.750 inches nominal
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations
-
Trip Release Method
magnetic all locations
-
Trip Release Characteristic
instantaneous all locations and time delay
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Auxiliary Switch Function And Quantity
3 control
-
Internal Trip Release Configuration
series trip all locations
-
Switch Location And Position Designation
external at pole two
-
Trip Delay Time In Seconds Per Rated Continuous Current
40.000 nominal at 200 pct all locations and 105.000 nominal at 200 pct and 6.000 nominal at 400 pct and 11.000 nominal at 400 pct
-
Switch Terminal Type
screw
-
Ultimate Trip Time Per Pole In Seconds
90.000 minimum all locations and 120.000 maximum
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.190 inches
-
Frequency In Hertz
50.0 all locations
-
Thread Series Designator
unf
-
Terminal Type And Quantity
6 screw