SW324

Circuit Breakers

CIRCUIT BREAKER

SW324

5925-00-943-4456

5925 - Circuit Breakers

The Technical Material Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    19b multipole-single actuator type

  • Center To Center Distance Between Terminals Parallel To Width

    1.000 inches nominal

  • Switch Contact Arrangement

    single pole, double throw

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    4 threaded stud

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Body Length

    5.250 inches nominal

  • Body Width

    3.000 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    4.359 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    3.062 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.000 inches nominal

  • Boss Height

    0.218 inches nominal

  • Mounting Surface To Terminal End Distance

    3.750 inches nominal

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac all locations

  • Trip Release Method

    magnetic all locations

  • Trip Release Characteristic

    instantaneous all locations and time delay

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole two

  • Auxiliary Switch Function And Quantity

    3 control

  • Internal Trip Release Configuration

    series trip all locations

  • Switch Location And Position Designation

    external at pole two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    40.000 nominal at 200 pct all locations and 105.000 nominal at 200 pct and 6.000 nominal at 400 pct and 11.000 nominal at 400 pct

  • Switch Terminal Type

    screw

  • Ultimate Trip Time Per Pole In Seconds

    90.000 minimum all locations and 120.000 maximum

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Nominal Thread Size

    0.190 inches

  • Frequency In Hertz

    50.0 all locations

  • Thread Series Designator

    unf

  • Terminal Type And Quantity

    6 screw

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...