ETM1579

Circuit Breakers

CIRCUIT BREAKER

ETM1579

5925-00-945-3478

5925 - Circuit Breakers

Spd Electrical Systems Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct all locations and 40.000 maximum at 200 pct all locations

  • Reset Method

    manual

  • Inclosure Protection Type For Which Designed

    dustproof

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Unpackaged Unit Weight

    3.750 pounds

  • Fragility Factor

    moderately rugged

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Frequency In Hertz

    400.0 all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.594 inches nominal

  • Body Length

    6.000 inches nominal

  • Boss Height

    0.219 inches nominal

  • Trip Release Ambient Temp Rating

    40.0 deg celsius maximum all locations

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Main Contact Tripping Mechanism Type

    trip free

  • Unthreaded Mounting Hole Diameter

    0.164 inches nominal

  • Terminal Type And Quantity

    6 compression

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Body Height

    3.594 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    5.125 inches nominal

  • Body Style

    multipole-single actuator type

  • Actuator Position Designation

    at pole two

  • Trip Release Method

    thermal-magnetic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Body Width

    4.500 inches nominal

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Maximum Continuous Load Current Rating Per Pole

    100.0 amperes ac all locations

  • Storage Type

    general purpose warehouse

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...