400695-1
Circuit Breakers
CIRCUIT BREAKER
400695-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
6 threaded stud
-
Center To Center Distance Between Terminals Parallel To Length
3.053 inches minimum and 3.073 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
1.021 inches minimum and 1.041 inches maximum
-
Switch Contact Arrangement
single pole,double throw
-
Arc Quenching Method
magnetic blowout
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Position Designation
at each pole
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Location And Position Designation
internal at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
5.000 minimum at 200 pct and 19.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Switch Current Rating And Type In Amps
5.0 ac and 1.0 dc
-
Frequency In Hertz
60.0
-
Body Length
3.709 inches minimum and 3.729 inches maximum
-
Body Width
3.042 inches minimum and 3.062 inches maximum
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and 2.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.021 inches minimum and 1.041 inches maximum
-
Fragility Factor
moderately rugged
-
Boss Height
0.146 inches minimum and 0.166 inches maximum
-
Mounting Surface To Terminal End Distance
3.239 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Switch Terminal Type
tab,solder lug
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Test Data Document
12909-400695 specification
-
Thread Series Designator
unc