13MC1-203-15

Circuit Breakers

CIRCUIT BREAKER

13MC1-203-15

5925-00-957-2388

5925 - Circuit Breakers

Sensata Technologies Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    multipole-multiple actuator type

  • Body Width

    2.250 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Boss Height

    0.140 inches nominal

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Arc Quenching Method

    air

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    magnetic-hydraulic

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Internal Trip Release Configuration

    series trip

  • Switch Location And Position Designation

    internal at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.300 minimum at 200 pct and 10.000 maximum at 200 pct

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Terminal Type And Quantity

    6 threaded stud

  • Body Length

    2.500 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Switch Contact Arrangement

    single pole,double throw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Trip Release Characteristic

    time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0

  • Manual Actuator Type And Quantity

    3 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • External Actuator Linkage Arrangement

    one,two,and three linked

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Nominal Thread Size

    0.138 inches

  • Switch Terminal Type

    turret

  • Switch Current Rating And Type In Amps

    5.0 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    125.0 ac and 50.0 dc

  • Frequency In Hertz

    400.0

  • Thread Series Designator

    unc

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.