MA7HKMG6-2-230VAC60C4

Circuit Breakers

CIRCUIT BREAKER

MA7HKMG6-2-230VAC60C4

5925-00-958-4332

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Manual Actuator Type And Quantity

    2 toggle

  • Mounting Surface To Terminal End Distance

    2.689 inches minimum and 2.813 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    2.0 amperes ac all locations

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Terminal Type And Quantity

    4 threaded stud

  • External Actuator Linkage Arrangement

    one and two linked

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Trip Delay Time In Seconds Per Rated Continuous Current

    4.000 minimum at 200 pct all locations and 10.000 maximum at 200 pct all locations

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Switch Terminal Type

    tab, solder lug

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Nominal Thread Size

    0.138 inches

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Operating Voltage Type And Rating Per Pole In Volts

    230.0 ac all locations

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Fragility Factor

    moderately rugged

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...