107-205-104
Circuit Breakers
CIRCUIT BREAKER
107-205-104
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac single location and 28.0 dc single location
-
Inclosure Protection Type For Which Designed
explosion proof
-
Overall Width
1.094 inches nominal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location and 15.0 amperes dc single location
-
Overall Height
0.750 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
116.0 single location
-
Overall Length
2.337 inches nominal
-
Trip Release Characteristic
instantaneous single location and time delay single location
-
Nominal Thread Size
0.469 inches
-
Thread Series Designator
uns
-
Case Material
plastic
-
~1
single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
900.000 maximum at 150 pct single location and 6.000 minimum at 300 pct single location and 50.000 maximum at 200 pct single location and 18.000 minimum at 200 pct single location and 60.000 minimum at 150 pct single location and 20.000 maximum at 300 pct
-
Manual Actuator Type And Quantity
1 toggle
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Arc Quenching Method
air
-
Trip Release Method
thermal single location
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Terminal Type And Quantity
2 screw
-
Actuator Function
trip-reset
-
Reset Method
manual
-
Specification/Standard Data
36659-613540-1 manufacturers specification