Q0B350
Circuit Breakers
CIRCUIT BREAKER
Q0B350
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 terminal
-
Circuit Protection Type
overcurrent all locations
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 minimum at 200 pct all locations and 30.000 maximum at 200 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Body Height
3.180 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.730 inches nominal
-
Case Material
plastic
-
Body Width
2.234 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Terminal Type And Quantity
3 clip and 3 compression
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Body Style
multipole-single actuator type
-
Body Length
3.000 inches nominal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Boss Height
0.160 inches nominal