AM12MG6-50-50VDC4
Circuit Breakers
CIRCUIT BREAKER
AM12MG6-50-50VDC4
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
12a single pole type
-
Case Material
plastic
-
Boss Height
0.140 inches nominal
-
Pole Quantity
1
-
Iii Storage Type
general purpose warehouse
-
Iii Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
magnetic-hydraulic single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Iii Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc single location
-
Trip Release Characteristic
time delay single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.500 minimum at 200 pct and 7.500 maximum at 200 pct single location
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Thread Series Designator
unc
-
Terminal Type And Quantity
2 threaded stud
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Iii Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
2.741 inches nominal
-
Body Length
2.500 inches nominal
-
Body Width
0.750 inches nominal