Technical Characteristics
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
55.000 maximum at 200 pct single location and 14.000 minimum at 300 pct single location and 26.000 maximum at 300 pct single location and 8.000 minimum at 400 pct single location and 200.000 maximum at 150 pct single location and 14.000 maximum at 400 pct
-
Terminal Type And Quantity
1 screw and 1 quick disconnect, male
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Circuit Protection Type
overcurrent single location
-
Special Features
mounting type is terminal
-
Pole Quantity
1
-
Overall Width
0.968 inches nominal
-
Arc Quenching Method
deion
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Release Method
thermal-magnetic single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Overall Height
2.921 inches nominal
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location
-
Frequency In Hertz
60.0 single location
-
Overall Length
2.843 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Trip Release Duty Cycle
continuous single location
-
Case Material
plastic
-
~1
single location and 30.000 minimum at 200 pc