2315739P55

Circuit Breakers

CIRCUIT BREAKER

2315739P55

5925-00-975-7348

5925 - Circuit Breakers

Navair And Navsea Managed

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    1b multipole-single actuator type

  • Bushing Length

    0.340 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.875 inches nominal

  • Pole Quantity

    3

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    230.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    reset

  • Special Test Features

    navord od36190

  • Thread Series Designator

    unef

  • Terminal Type And Quantity

    6 wire hook

  • Reference Number Differentiating Characteristics

    as differentiated by special test features

  • Body Length

    1.875 inches nominal

  • Body Width

    1.531 inches nominal

  • Case Material

    metal

  • Center To Center Distance Between Terminals Parallel To Length

    0.625 inches nominal

  • Mounting Surface To Terminal End Distance

    1.855 inches nominal

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Maximum Continuous Load Current Rating Per Pole

    7.5 amperes ac all locations

  • Trip Release Method

    magnetic all locations

  • Ultimate Trip Time Per Pole In Seconds

    0.500 minimum all locations and 5.000 maximum

  • Reset Method

    manual

  • Actuator Position Designation

    at each pole

  • Internal Trip Release Configuration

    series trip all locations

  • Nominal Thread Size

    0.375 inches

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.100 minimum at 200 pct all locations and 1.200 maximum at 200 pct and 0.030 minimum at 300 pct and 0.440 maximum at 300 pct and 0.010 minimum at 400 pct and 0.210 maximum at 400 pct

  • Inclosure Protection Type For Which Designed

    hermetically sealed

  • Frequency In Hertz

    400.0 all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...