Technical Characteristics
-
Actuator Function
reset
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Adjustable Trip Setting Current Range Per Pole In Amps
+525.0/+950.0 ac all locations and +525.0/+950.0 dc all locations
-
Actuator Position Designation
at each pole
-
Body Width
4.125 inches nominal
-
Reset Method
manual
-
Features Provided
adjustable trip release
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 250.0 dc all locations
-
Body Length
6.500 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.312 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.938 inches nominal
-
Trip Release Method
thermal-magnetic all locations
-
Unthreaded Mounting Hole Diameter
0.281 inches nominal
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Terminal Type And Quantity
6 quick disconnect, female
-
Frequency In Hertz
60.0 all locations
-
Body Height
4.125 inches nominal
-
Boss Height
0.188 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations and 10000.0 dc all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.688 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
75.0 amperes ac all locations and 75.0 amperes dc all locations
-
Case Material
plastic