Technical Characteristics
-
Switch Voltage Rating And Type In Volts
250.0 ac and 125.0 dc
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 threaded stud
-
Center To Center Distance Between Terminals Parallel To Length
4.344 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Pole Quantity
3
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Time Per Pole In Seconds
1.500 minimum all locations and 7.000 maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.300 minimum at 200 pct all locations and 1.100 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Switch Current Rating And Type In Amps
15.0 ac and 0.5 dc
-
Body Style
17b multipole-single actuator type
-
Body Width
2.984 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
0.984 inches nominal
-
Unthreaded Mounting Hole Diameter
0.190 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.359 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.984 inches nominal
-
Boss Height
0.218 inches nominal
-
Mounting Surface To Terminal End Distance
3.500 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Reset Method
manual
-
Auxiliary Switch Function And Quantity
1 control
-
Switch Location And Position Designation
external at pole three
-
Switch Terminal Type
screw
-
Unpackaged Unit Weight
1.750 pounds
-
Body Length
5.250 inches nominal