Technical Characteristics
-
Actuator Function
reset
-
Fragility Factor
moderately rugged
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location and 1000.0 dc single location
-
Storage Type
general purpose warehouse
-
Center To Center Distance Between Terminals Parallel To Length
0.850 inches nominal
-
Unpackaged Unit Weight
1.500 ounces
-
Manual Actuator Type And Quantity
1 push button
-
Body Width
0.660 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 single location
-
Nominal Thread Size
0.438 inches
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Arc Quenching Method
air
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Body Length
1.375 inches nominal
-
Pole Quantity
1
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof
-
Mounting Surface To Terminal End Distance
1.815 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct single location and 45.000 maximum at 200 pct single location
-
Maximum Continuous Load Current Rating Per Pole
1.0 amperes ac single location and 1.0 amperes dc single location
-
Terminal Type And Quantity
2 quick disconnect, male
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Thread Series Designator
unef
-
Bushing Length
0.500 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location and 50.0 dc single location
-
Thread Quantity Per Inch
28
-
Case Material
plastic