NEF433050

Circuit Breakers

CIRCUIT BREAKER

NEF433050

5925-01-025-0320

5925 - Circuit Breakers

Challenger Electrical Equipment Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Body Length

    6.062 inches nominal

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac all locations

  • Body Width

    4.125 inches nominal

  • Reset Method

    manual

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Unthreaded Mounting Hole Diameter

    0.225 inches nominal

  • Trip Release Characteristic

    instantaneous all locations and time delay all locations

  • Packaged Unit Weight

    4.000 pounds

  • Trip Delay Time In Seconds Per Rated Continuous Current

    12.000 minimum at 200 pct all locations and 35.000 maximum at 200 pct all locations

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.125 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Actuator Position Designation

    at pole two

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Body Style

    multipole-single actuator type

  • Boss Height

    0.250 inches nominal

  • Manual Actuator Type And Quantity

    1 toggle

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 compression

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac all locations

  • Arc Quenching Method

    magnetic blowout

  • Center To Center Distance Between Terminals Parallel To Length

    5.219 inches nominal

  • Inclosure Protection Type For Which Designed

    general purpose

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.375 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations

  • Body Height

    3.406 inches nominal

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...