AP1-1R-3062-2

Circuit Breakers

CIRCUIT BREAKER

AP1-1R-3062-2

5925-01-029-3481

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Length

    0.906 inches maximum

  • Inclosure Protection Type For Which Designed

    moisture resistant and shock resistant and vibration resistant and fungus resistant and salt spray proof

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.200 minimum at 200 pct single location and 6.000 maximum at 200 pct single location

  • Frequency In Hertz

    400.0 single location

  • Switch Current Rating And Type In Amps

    0.5 ac and 0.5 dc

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Release Characteristic

    time delay single location

  • Maximum Continuous Load Current Rating Per Pole

    500.0 milliamperes ac single location

  • Internal Trip Release Configuration

    series trip single location

  • Manual Actuator Type And Quantity

    1 toggle

  • Nonturn Device Radius

    0.625 inches nominal

  • Pole Quantity

    1

  • Switch Contact Arrangement

    single pole, double throw

  • Body Length

    1.281 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Thread Quantity Per Inch

    32

  • Nominal Thread Size

    0.375 inches

  • Thread Pitch Diameters

    +0.3503/+0.3537 inches

  • Nonturn Device Location

    at 12 oclock

  • Mounting Surface To Terminal End Distance

    1.828 inches maximum

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Reset Method

    manual

  • Test Data Document

    10001-3179574 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)

  • Bushing Length

    0.280 inches minimum and 0.380 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac single location

  • Special Handling Feature

    magnetic

  • Terminal Type And Quantity

    2 wire hook

  • Trip Release Method

    magnetic single location

  • Fragility Factor

    moderately rugged

  • Body Style

    single pole type

  • Body Width

    0.625 inches maximum

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    138.0 single location

  • Switch Terminal Type

    pin

  • Nonturn Device Diameter

    0.180 inches minimum and 0.300 inches maximum

  • Thread Series Designator

    unef

  • Switch Voltage Rating And Type In Volts

    120.0 ac and 50.0 dc

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.