2263S10-250VAC2

Circuit Breakers

CIRCUIT BREAKER

2263S10-250VAC2

5925-01-030-5502

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Length

    5.250 inches nominal

  • Body Width

    2.000 inches nominal

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    3.062 inches nominal

  • Fragility Factor

    moderately rugged

  • Boss Height

    0.218 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0

  • Main Contact Tripping Mechanism Type

    trip free

  • Internal Trip Release Configuration

    series trip

  • Nominal Thread Size

    0.138 inches

  • Inclosure Protection Type For Which Designed

    dustproof

  • Frequency In Hertz

    60.0

  • Thread Series Designator

    unc

  • Body Style

    multipole-single actuator type

  • Body Height

    2.687 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    4.359 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.984 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.984 inches nominal

  • Arc Quenching Method

    air

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    magnetic-hydraulic

  • Trip Release Characteristic

    time delay

  • Reset Method

    manual

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    5.500 minimum at 200 pct and 20.000 maximum at 200 pct

  • Terminal Type And Quantity

    4 screw

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...