UPGX-14-1404-1
Circuit Breakers
CIRCUIT BREAKER
UPGX-14-1404-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac first location
-
Terminal Type And Quantity
4 tab, solder lug
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.400 minimum at 200 pct first location and 1.000 maximum at 200 pct first location
-
Inclosure Protection Type For Which Designed
shockproof and corrosion resistant and moisture resistant and vibrationproof
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Surface To Terminal End Distance
2.390 inches maximum
-
Body Length
2.590 inches nominal
-
Nominal Thread Size
0.138 inches
-
Manual Actuator Type And Quantity
1 rotary
-
Body Style
multipole-single actuator type
-
Actuator Position Designation
at pole two
-
Maximum Continuous Load Current Rating Per Pole
50.0 milliamperes dc second location
-
Internal Trip Release Configuration
series trip first location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
magnetic all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations and 1000.0 dc all locations
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
4 threaded hole
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Precious Material
silver
-
Reset Method
manual
-
Thread Series Designator
unc
-
Unpackaged Unit Weight
4.400 ounces
-
Pole Quantity
2
-
Internal Trip Release Configuration
relay trip second location
-
Circuit Protection Type
overcurrent all locations
-
Special Handling Feature
magnetic
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Fragility Factor
moderately rugged
-
Case Material
plastic
-
Body Width
1.515 inches nominal
-
Bushing Length
0.130 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.010 minimum at 200 pct second location and 0.040 maximum at 200 pct second location
-
Operating Voltage Type And Rating Per Pole In Volts
20.0 dc second location
-
Precious Material And Location
contact and terminal surfaces silver
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac first location