AM1-Z26-48
Circuit Breakers
CIRCUIT BREAKER
AM1-Z26-48
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performanc
-
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Specification/Standard Data
81349-mil-c-55629/2 government specification
-
Fragility Factor
moderately rugged
-
Body Width
0.730 inches minimum and 0.780 inches maximum
-
Trip Release Method
magnetic single location
-
Switch Terminal Type
tab, solder lug
-
Center To Center Distance Between Terminals Parallel To Length
1.660 inches minimum and 1.960 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.046 inches minimum and 2.078 inches maximum
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
2 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac single location
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Switch Current Rating And Type In Amps
10.0 ac and 2.0 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct single location and 1.900 maximum at 200 pct single location
-
Mounting Surface To Terminal End Distance
2.800 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Frequency In Hertz
400.0 single location
-
Body Style
single pole type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 single location
-
Auxiliary Switch Function And Quantity
1 alarm
-
Body Length
2.510 inches maximum
-
Boss Height
0.109 inches minimum and 0.171 inches maximum
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud