Technical Characteristics
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
6 threaded hole and 6 slot
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
40.0 dc third location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac and 5000.0 dc all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip first location
-
Internal Trip Release Configuration
series trip second location
-
Internal Trip Release Configuration
shunt trip third location
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Pole Quantity
3
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.994 inches minimum and 1.058 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.994 inches minimum and 1.058 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
3.515 inches minimum and 3.579 inches maximum
-
Case Material
plastic
-
Body Width
3.046 inches minimum and 3.110 inches maximum
-
Body Length
5.768 inches minimum and 5.832 inches maximum
-
Mounting Slot Width
0.164 inches nominal
-
Body Style
8c multipole-multiple actuator type
-
Mounting Surface To Terminal End Distance
3.172 inches minimum and 3.296 inches maximum
-
Fragility Factor
moderately rugged
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes dc second location
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes ac first location
-
Boss Height
0.187 inches minimum and 0.251 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.718 inches minimum and 2.782 inches maximum
-
Frequency In Hertz
60.0
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Switch Current Rating And Type In Amps
5.0 ac and 1.0 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
5.500 minimum at 200 pct and 19.000 maximum at 200 pct all locations
-
Switch Location And Position Designation
internal at pole two
-
Auxiliary Switch Function And Quantity
1 alarm
-
Actuator Position Designation
at each pole
-
Manual Actuator Type And Quantity
3 toggle
-
Reset Method
manual
-
Trip Release Method
magnetic-hydraulic all locations
-
Circuit Protection Type
overcurrent all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac first location
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc second location
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes dc third location