CD1-B3-20-3
Circuit Breakers
CIRCUIT BREAKER
CD1-B3-20-3
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Thread Series Designator
unc
-
Terminal Type And Quantity
2 threaded stud
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.140 minimum at 200 pct single location and 0.750 maximum at 200 pct
-
Body Style
12a single pole type
-
Mounting Slot Width
0.218 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.490 inches minimum and 3.510 inches maximum
-
Fragility Factor
moderately rugged
-
Boss Height
0.209 inches minimum and 0.229 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Inclosure Protection Type For Which Designed
dustproof
-
Body Length
5.790 inches minimum and 5.810 inches maximum
-
Body Width
1.016 inches minimum and 1.036 inches maximum
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and 2.760 inches maximum
-
Mounting Surface To Terminal End Distance
3.115 inches minimum and 3.135 inches maximum
-
Pole Quantity
1
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole and 2 slot
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc single location
-
Trip Release Method
magnetic-hydraulic single location
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole one
-
Nominal Thread Size
0.138 inches