JA2A8-30-0-6-2
Circuit Breakers
CIRCUIT BREAKER
JA2A8-30-0-6-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
2.000 inches nominal
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Fragility Factor
moderately rugged
-
Arc Quenching Method
magnetic blowout
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Trip Release Method
magnetic-hydraulic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
External Actuator Linkage Arrangement
one and two linked
-
Internal Trip Release Configuration
series trip
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Frequency In Hertz
50.0 or b60.0
-
Unpackaged Unit Weight
4.400 ounces
-
Terminal Type And Quantity
4 quick disconnect,male
-
Body Width
1.500 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.560 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Boss Height
0.130 inches nominal
-
Mounting Surface To Terminal End Distance
1.843 inches nominal
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Features Provided
high inrush protection
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct
-
Thread Series Designator
unc