JA1-A8-A-2-20
Circuit Breakers
CIRCUIT BREAKER
JA1-A8-A-2-20
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
0.745 inches minimum and 0.755 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.555 inches minimum and 1.565 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.655 inches minimum and 1.665 inches maximum
-
Boss Height
0.125 inches minimum and 0.135 inches maximum
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
2 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 20.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
dustproof
-
Thread Series Designator
unc
-
Terminal Type And Quantity
2 tab,solder lug
-
Mounting Surface To Terminal End Distance
1.875 inches minimum and 1.885 inches maximum
-
Arc Quenching Method
air
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
60.0
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Case Material
plastic
-
Fragility Factor
moderately rugged