Technical Characteristics

  • Inclosure Protection Type For Which Designed

    dustproof

  • Frequency In Hertz

    60.0 all locations

  • Thread Series Designator

    iso s

  • Body Style

    8c multipole-multiple actuator type

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches maximum

  • Boss Height

    0.150 inches nominal

  • Mounting Surface To Terminal End Distance

    2.825 inches maximum

  • Arc Quenching Method

    magnetic blowout

  • Storage Type

    unimproved open

  • Thread Quantity Per Inch

    32

  • Maximum Continuous Load Current Rating Per Pole

    500.0 milliamperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Trip Release Method

    magnetic all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Nominal Thread Size

    3.0 millimeters

  • Thread Pitch In Millimeters

    0.50

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    3 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at each pole

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.180 minimum at 200 pct all locations and 1.800 maximum at 200 pct

  • Unpackaged Unit Weight

    12.750 ounces

  • Terminal Type And Quantity

    6 threaded stud

  • Body Length

    2.490 inches nominal

  • Body Width

    2.250 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.060 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches maximum

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Ultimate Trip Time Per Pole In Seconds

    12.000 maximum all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...