219-3-1-63F-5-8-20A
Circuit Breakers
CIRCUIT BREAKER
219-3-1-63F-5-8-20A
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
3.108 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.550 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.026 inches nominal
-
Mounting Surface To Terminal End Distance
3.550 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
70.000 minimum at 125 pct and 20.000 minimum at 200 pct and 4.000 minimum at 400 pct and 0.012 minimum at 1000 pct
-
Body Length
5.800 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
1.026 inches nominal
-
Boss Height
0.220 inches nominal
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac
-
Trip Release Method
magnetic-hydraulic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Internal Trip Release Configuration
series trip
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Frequency In Hertz
60.0
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud