1314479-1
Circuit Breakers
CIRCUIT BREAKER
1314479-1
Northrop Grumman Systems Corporation
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
1.500 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac second location
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Unpackaged Unit Weight
3.600 ounces
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.100 minimum at 200 pct second location and 0.700 maximum at 200 pct second location
-
Body Width
1.250 inches maximum
-
Thread Series Designator
unef
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
120.0 first location
-
Inclosure Protection Type For Which Designed
shockproof and hermetically sealed and vibrationproof
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac second location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac second location
-
Center To Center Distance Between Terminals Parallel To Width
0.344 inches minimum and 0.406 inches maximum
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Circuit Protection Type
overcurrent second location
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Frequency In Hertz
60.0 second location
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Internal Trip Release Configuration
series trip first location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc first location
-
Nonturn Device Location
at 3 oclock and at 9 oclock
-
Body Style
multipole-single actuator type
-
Trip Release Characteristic
instantaneous first location
-
Case Material
metal
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc first location
-
Manual Actuator Type And Quantity
1 toggle
-
Circuit Protection Type
overvoltage first location
-
Trip Release Characteristic
time delay second location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 second location
-
Fragility Factor
moderately rugged
-
Nonturn Device Diameter
0.250 inches nominal
-
Special Handling Feature
magnetic
-
Center To Center Distance Between Terminals Parallel To Length
0.594 inches minimum and 0.656 inches maximum
-
Internal Trip Release Configuration
relay trip second location
-
Pole Quantity
2
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes dc first location
-
Terminal Type And Quantity
5 wire hook
-
Bushing Length
0.332 inches minimum and 0.380 inches maximum