AM1-A3-15-250AC-

Circuit Breakers

CIRCUIT BREAKER

AM1-A3-15-250AC-

5925-01-064-4097

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Release Method

    magnetic-hydraulic single location

  • Body Style

    single pole type

  • Frequency In Hertz

    50.0 single location or 60.0 single location

  • Arc Quenching Method

    magnetic blowout

  • Main Contact Tripping Mechanism Type

    trip free

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Boss Height

    0.140 inches minimum and 0.160 inches maximum

  • Trip Release Characteristic

    time delay single location

  • Nominal Thread Size

    0.138 inches

  • Internal Trip Release Configuration

    series trip single location

  • Manual Actuator Type And Quantity

    1 toggle

  • Pole Quantity

    1

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac single location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac single location

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Circuit Protection Type

    overcurrent single location

  • Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Thread Quantity Per Inch

    32

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.050 inches minimum and 2.070 inches maximum

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Actuator Position Designation

    at pole one

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Reset Method

    manual

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac single location

  • Terminal Type And Quantity

    2 threaded stud

  • Case Material

    plastic

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Unpackaged Unit Weight

    4.250 ounces

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.030 minimum at 400 pct single location and 0.003 minimum at 1000 pct single location and 1.500 maximum at 200 pct single location and 0.150 minimum at 200 pct single location and 0.450 maximum at 300 pct single location and 0.230 maximum at 400 pct

  • Thread Series Designator

    unc

  • Fragility Factor

    moderately rugged

  • ~1

    single location and 0.055 minimum at 300 pct sing

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...