Circuit Breakers

CIRCUIT BREAKER

AM3-A3-10-2

5925-01-064-7822

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 maximum at 200 pct all locations and 2.000 minimum at 200 pct all locations and 0.300 minimum at 400 pct all locations and 0.600 minimum at 300 pct all locations and 2.000 maximum at 400 pct all locations and 5.000 maximum at 300 pct all locations

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Manual Actuator Type And Quantity

    3 toggle

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • ~1

    and 0.005 minimum at 1000 pct all locations a

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Surface To Terminal End Distance

    2.331 inches minimum and 2.492 inches maximum

  • Actuator Position Designation

    at each pole

  • Thread Series Designator

    unc

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Fragility Factor

    moderately rugged

  • Ultimate Trip Time Per Pole In Seconds

    10.000 minimum all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Arc Quenching Method

    magnetic blowout

  • Main Contact Tripping Mechanism Type

    trip free

  • Frequency In Hertz

    50.0 all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Nominal Thread Size

    0.138 inches

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac all locations

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Unpackaged Unit Weight

    12.750 ounces

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Body Width

    2.240 inches minimum and 2.260 inches maximum

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic-hydraulic all locations

  • Thread Quantity Per Inch

    32

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..