AM1-C3-3-2
Circuit Breakers
CIRCUIT BREAKER
AM1-C3-3-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Actuator Position Designation
at pole one
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac single location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Frequency In Hertz
400.0 single location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Body Style
single pole type
-
Trip Release Method
magnetic-hydraulic single location
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Ultimate Trip Time Per Pole In Seconds
9.000 minimum single location
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Fragility Factor
moderately rugged
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 single location
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct single location and 3.000 maximum at 400 pct single location and 0.800 minimum at 300 pct single location and 6.000 maximum at 300 pct single location and 0.400 minimum at 400 pct single location and 20.000 maximum at 200 pct
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
~1
single location and 0.100 minimum at 500 pct sing