UPL-1-1-62-203
Circuit Breakers
CIRCUIT BREAKER
UPL-1-1-62-203
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
2.480 inches minimum and 2.500 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.925 inches minimum and 1.955 inches maximum
-
Mounting Surface To Terminal End Distance
2.490 inches maximum
-
Arc Quenching Method
magnetic blowout
-
Thread Series Designator
unc
-
Body Style
caaql 12a
-
Body Width
0.750 inches maximum
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Fragility Factor
moderately rugged
-
Boss Height
0.135 inches minimum and 0.165 inches maximum
-
Pole Quantity
1
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac .
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac .
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac .
-
Circuit Protection Type
overcurrent .
-
Trip Release Characteristic
time delay .
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 22.000 maximum at 200 pct .
-
Mounting Facility Type And Quantity
2 threaded hole
-
Special Handling Feature
magnetic
-
Trip Release Method
magnetic-hydraulic .
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Internal Trip Release Configuration
series trip .
-
Inclosure Protection Type For Which Designed
moisture resistant and salt spray proof and shock resistant and vibration resistant
-
Frequency In Hertz
50.0 or 60.0
-
Unpackaged Unit Weight
3.700 ounces
-
Terminal Type And Quantity
2 threaded stud