5012279-03
Circuit Breakers
CIRCUIT BREAKER
5012279-03
Thales Training & Simulation Ltd
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Arc Quenching Method
air
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Pole Quantity
1
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Body Style
single pole type
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac single location
-
Trip Release Method
magnetic-hydraulic single location
-
Frequency In Hertz
60.0 single location
-
Unpackaged Unit Weight
3.000 ounces
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Inclosure Protection Type For Which Designed
moisture resistant and fungus proof and vibrationproof
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum