AM333-25-250-4-60
Circuit Breakers
CIRCUIT BREAKER
AM333-25-250-4-60
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Width
2.240 inches minimum and 2.260 inches maximum
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Unpackaged Unit Weight
12.750 ounces
-
Mounting Facility Type And Quantity
6 threaded hole
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.370 minimum at 500 pct all locations and 1.500 minimum at 300 pct all locations and 0.600 minimum at 400 pct all locations and 4.000 maximum at 300 pct all locations and 2.000 maximum at 400 pct all locations and 1.100 maximum at 500 pct all locations
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Manual Actuator Type And Quantity
3 toggle
-
Ultimate Trip Time Per Pole In Seconds
17.000 minimum all locations and 80.000 maximum all locations
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Mounting Surface To Terminal End Distance
2.539 inches minimum and 2.683 inches maximum
-
Terminal Type And Quantity
6 threaded stud