HE2-A3-5-2
Circuit Breakers
CIRCUIT BREAKER
HE2-A3-5-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Special Features
hermetically sealed case
-
Body Style
multipole-single actuator type
-
Case Material
metal
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Bushing Length
0.375 inches nominal
-
Body Length
1.562 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Thread Series Designator
unef
-
Mounting Surface To Terminal End Distance
1.700 inches maximum
-
Body Width
1.281 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.007 minimum at 500 pct all locations and 0.150 minimum at 200 pct all locations and 0.700 maximum at 200 pct all locations and 0.040 maximum at 500 pct all locations
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Facility Type And Quantity
thd bushing w/panel seal
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Terminal Type And Quantity
4 wire hook