M55629/5-021

Circuit Breakers

CIRCUIT BREAKER

M55629/5-021

5925-01-073-8952

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Test Data Document

    81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

  • ~1

    data on certain environmental and performanc

  • Inclosure Protection Type For Which Designed

    shock resistant and vibration resistant

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.046 inches minimum and 2.078 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Surface To Terminal End Distance

    2.522 inches minimum and 2.553 inches maximum

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Body Width

    2.205 inches minimum and 2.285 inches maximum

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Circuit Protection Type

    overcurrent all locations

  • Nominal Thread Size

    0.138 inches

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Boss Height

    0.140 inches nominal

  • Frequency In Hertz

    400.0 all locations

  • Specification/Standard Data

    81349-mil-c-55629/5 government specification

  • Body Length

    2.510 inches maximum

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.100 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations

  • Manual Actuator Type And Quantity

    3 toggle

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • Maximum Continuous Load Current Rating Per Pole

    1.0 amperes ac all locations

  • Fragility Factor

    moderately rugged

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.660 inches minimum and 1.960 inches maximum

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...