TLPN50330
Circuit Breakers
CIRCUIT BREAKER
TLPN50330
L-3 Communications Corporation
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac first location
-
Fragility Factor
moderately rugged
-
Unpackaged Unit Weight
1.200 pounds
-
Trip Release Characteristic
instantaneous all locations
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Frequency In Hertz
400.0 first location
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Frequency In Hertz
50.0 third location or 60.0 third location
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Mounting Surface To Terminal End Distance
2.331 inches minimum and 2.492 inches maximum
-
Thread Quantity Per Inch
32
-
Mounting Facility Type And Quantity
8 threaded hole
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac second location
-
External Actuator Linkage Arrangement
one, two, three, and four linked
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 fourth location
-
Terminal Type And Quantity
8 threaded stud
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac fourth location
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Frequency In Hertz
400.0 second location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 first location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 third location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 second location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Body Width
2.990 inches minimum and 3.010 inches maximum
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac third location
-
Manual Actuator Type And Quantity
4 toggle
-
Frequency In Hertz
50.0 fourth location or 60.0 fourth location
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Pole Quantity
4