JB1-A8-A-20-2
Circuit Breakers
CIRCUIT BREAKER
JB1-A8-A-20-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 clip
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.500 minimum at 200 pct single location and 20.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Terminal Type And Quantity
2 quick disconnect, male
-
Body Style
10a single pole type
-
Body Length
2.418 inches minimum and 2.482 inches maximum
-
Body Width
0.923 inches minimum and 0.987 inches maximum
-
Body Height
1.811 inches minimum and 1.875 inches maximum
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Boss Height
0.093 inches minimum and 0.157 inches maximum
-
Pole Quantity
1
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location
-
Trip Release Method
magnetic-hydraulic single location
-
Trip Release Characteristic
time delay single location
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip single location
-
Frequency In Hertz
50.0 single location or 60.0
-
Unpackaged Unit Weight
0.156 pounds