CB68A15

Circuit Breakers

CIRCUIT BREAKER

CB68A15

5925-01-085-1214

5925 - Circuit Breakers

Cae-Link Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Terminal Type And Quantity

    6 threaded stud

  • Fragility Factor

    moderately rugged

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Body Width

    2.220 inches minimum and 2.280 inches maximum

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Mounting Surface To Terminal End Distance

    2.409 inches minimum and 2.533 inches maximum

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Unpackaged Unit Weight

    0.625 pounds

  • Arc Quenching Method

    magnetic blowout

  • Body Length

    2.500 inches nominal

  • Boss Height

    0.140 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Manual Actuator Type And Quantity

    3 toggle

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...