ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
22.000 minimum at 200 pct and 105.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
shockproof and vibrationproof
-
Frequency In Hertz
60.0
-
Unpackaged Unit Weight
0.690 pounds
-
Terminal Type And Quantity
2 threaded stud
-
Body Width
0.990 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac
-
Body Length
3.719 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
3.063 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Fragility Factor
moderately rugged
-
Boss Height
0.156 inches nominal
-
Mounting Surface To Terminal End Distance
3.239 inches nominal
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
2 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Thread Series Designator
unc