APGN-111-1-66-203

Circuit Breakers

CIRCUIT BREAKER

APGN-111-1-66-203

5925-01-093-9454

5925 - Circuit Breakers

Sensata Technologies Maryland Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Terminal Type And Quantity

    6 quick disconnect, male

  • Mounting Surface To Terminal End Distance

    2.232 inches maximum

  • Frequency In Hertz

    50.0 all locations or 60.0 all locations

  • Nonturn Device Radius

    0.641 inches minimum and 0.671 inches maximum

  • Bushing Length

    0.480 inches minimum and 0.510 inches maximum

  • Thread Series Designator

    un

  • Inclosure Protection Type For Which Designed

    shock resistant and moisture resistant and salt spray proof and vibration resistant

  • Nonturn Device Length

    0.115 inches minimum and 0.145 inches maximum

  • Unpackaged Unit Weight

    9.000 ounces

  • Case Material

    plastic

  • Maximum Continuous Load Current Rating Per Pole

    20.0 amperes ac all locations

  • Internal Trip Release Configuration

    series trip all locations

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Storage Type

    general purpose warehouse

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Nominal Thread Size

    0.500 inches

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Length

    1.515 inches minimum and 1.545 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    0.735 inches minimum and 0.765 inches maximum

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Special Handling Feature

    magnetic

  • Trip Delay Time In Seconds Per Rated Continuous Current

    10.000 minimum at 200 pct all locations and 70.000 maximum at 200 pct all locations

  • Thread Quantity Per Inch

    32

  • Body Length

    1.985 inches minimum and 2.015 inches maximum

  • Trip Release Method

    magnetic-hydraulic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Actuator Position Designation

    at pole two

  • Nonturn Device Diameter

    0.151 inches minimum and 0.161 inches maximum

  • Body Style

    multipole-single actuator type

  • Body Width

    2.265 inches maximum

  • Manual Actuator Type And Quantity

    1 toggle

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Operating Voltage Type And Rating Per Pole In Volts

    277.0 ac all locations

  • Fragility Factor

    moderately rugged

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.