W-C-375/19
Circuit Breakers
CIRCUIT BREAKER
W-C-375/19
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
120.000 maximum at 200 pct
-
Frequency In Hertz
60.0
-
Test Data Document
81348-w-c-375 specification
-
Terminal Type And Quantity
2 screw
-
Specification/Standard Data
81348-w-c-375/9 government specification
-
Body Length
4.750 inches minimum and 4.760 inches maximum
-
Body Width
1.015 inches minimum and 1.035 inches maximum
-
Body Height
2.599 inches minimum and 2.619 inches maximum
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
4.370 inches minimum and 4.390 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.740 inches minimum and 2.760 inches maximum
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
2 threaded hole
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac
-
Trip Release Method
magnetic
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
dustproof
-
Thread Series Designator
unc
-
Fragility Factor
moderately rugged
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one