W-C-375/16

Circuit Breakers

CIRCUIT BREAKER

W-C-375/16

5925-01-096-4692

5925 - Circuit Breakers

Federal Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Mounting Slot Width

    0.168 inches minimum and 0.198 inches maximum

  • Case Material

    plastic

  • Boss Height

    0.115 inches minimum and 0.135 inches maximum

  • Pole Quantity

    1

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    4 slot

  • Storage Type

    general purpose warehouse

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Terminal Type And Quantity

    2 compression

  • Specification/Standard Data

    81348-w-c-375/16 government specification

  • Body Length

    5.990 inches minimum and 6.010 inches maximum

  • Body Width

    1.365 inches minimum and 1.385 inches maximum

  • Body Height

    3.365 inches minimum and 3.385 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    5.052 inches minimum and 5.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.490 inches minimum and 4.510 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.990 inches minimum and 1.010 inches maximum

  • Fragility Factor

    moderately rugged

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    14000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    thermal-magnetic

  • Trip Release Characteristic

    time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    360.000 maximum at 200 pct

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal

  • Frequency In Hertz

    60.0

  • Test Data Document

    81348-w-c-375 specification

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...