CD3-A3A2A2-AB-40-480-2

Circuit Breakers

CIRCUIT BREAKER

CD3-A3A2A2-AB-40-480-2

5925-01-099-0970

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Location And Position Designation

    internal at pole two and internal at pole three

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Center To Center Distance Between Terminals Parallel To Length

    3.546 inches nominal

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic-hydraulic all locations

  • Center To Center Distance Between Terminals Parallel To Width

    1.032 inches nominal

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.609 inches nominal

  • Internal Trip Release Configuration

    series trip all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Storage Type

    general purpose warehouse

  • Mounting Facility Type And Quantity

    6 threaded hole and 6 slot

  • Auxiliary Switch Function And Quantity

    2 alarm

  • Reset Method

    manual

  • Actuator Position Designation

    at each pole

  • Thread Series Designator

    unc

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • Special Handling Feature

    magnetic

  • Switch Terminal Type

    tab, solder lug

  • Fragility Factor

    moderately rugged

  • Switch Current Rating And Type In Amps

    10.0 ac and 4.0 dc

  • Maximum Continuous Load Current Rating Per Pole

    40.0 amperes ac all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Boss Height

    0.218 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.750 inches nominal

  • Mounting Slot Width

    0.164 inches nominal

  • Manual Actuator Type And Quantity

    3 toggle

  • Body Length

    5.840 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    5.500 minimum at 200 pct all locations and 19.000 maximum at 200 pct all locations

  • Unpackaged Unit Weight

    2.000 pounds

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.032 inches nominal

  • Case Material

    plastic

  • Body Width

    3.093 inches nominal

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...