Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.150 minimum at 200 pct and 1.500 maximum at 200 pct

  • Auxiliary Switch Function And Quantity

    1 alarm

  • External Actuator Linkage Arrangement

    one and two linked

  • Actuator Position Designation

    at each pole

  • Actuator Function

    trip-reset

  • Reset Method

    manual

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Trip Release Characteristic

    time delay

  • Trip Release Method

    magnetic-hydraulic

  • Circuit Protection Type

    overcurrent

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac

  • Maximum Continuous Load Current Rating Per Pole

    25.0 amperes ac

  • Special Handling Feature

    magnetic

  • Arc Quenching Method

    magnetic blowout

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Fragility Factor

    moderately rugged

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Switch Contact Arrangement

    single pole,double throw

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Thread Series Designator

    unc

  • Frequency In Hertz

    50.0 or b60.0

  • Switch Terminal Type

    quick disconnect,male

  • Switch Location And Position Designation

    internal at pole one

  • Nominal Thread Size

    0.138 inches

  • Internal Trip Release Configuration

    series trip

  • Manual Actuator Type And Quantity

    2 toggle

  • Main Contact Tripping Mechanism Type

    trip free

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac

  • Thread Quantity Per Inch

    32

  • Storage Type

    general purpose warehouse

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Pole Quantity

    2

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Case Material

    plastic

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Terminal Type And Quantity

    4 threaded stud

  • Unpackaged Unit Weight

    6.500 ounces

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 30.0 dc

  • Switch Current Rating And Type In Amps

    10.0 ac and 4.0 dc

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...